If you have any questions, please contact us.

Get in touch
Home Products Power Distribution System Series GZX 12kV~40.5kV Cubicle Type Gas Insulated Switchgear (C-GIS)

Series GZX 12kV~40.5kV Cubicle Type Gas Insulated Switchgear (C-GIS)

Series GZX 12kV~40.5kV Cubicle Type Gas Insulated Switchgear (C-GIS)
Product Overview

Cubicle type metal claded Gas Insulated Switchgear, called as C-GIS, developing from 90's of 20 century, focusing on modularizing, multifunction, high reliably and compact structure, has achieved preeminence on technical, economical and ecological environmental.Now C-GIS is representing the development direction of MV switchgears and world advanced level on technology, and becoming animportant branch of MV metal clad switchgear.It expands conventional GIS' stechnology to MV area and adopts low pressure SF₆ gas or mixed gas of SF₆ and N₂ as insulation medium. Combines the technology of GIS and switchgear to form a new series of gas insulated metal clad switchgears.

GZX series C-GIS using SF gas as insulation medium, with stainless steel housing which hermetically sealed and being of fixed style switch board belongs to indoor switchgear assemblies of AC three phase single busbar or sectionalizing single busbar, aremainly used in power distribution system of auxiliary power network in power plants, middle and small size generators, substations, high buildings, industrial and mining enterprises, subway projects. etc. to carry out the control, protection and measuring and checking for distribution system and loads. It is suitable used specially in such location like underground, altiplano, frozen earth, littoral and humidification area, and population crowded districts and architecture expensive places.

Rating of GZX0 and GZX2 type cubicle

Electric parameters

Unit

GZX0

GZX2

Rated voltage

kV

12

40.5

Rated power frequency withstand voltage(1min)

kV

42/48

95/118

Rated lightning impulse withstand voltage(peak)

kV

75/85

185/215

Rated frequency

Hz

50

Rated current

A

630

1250

1250

2500

Rated short time withstand current 4s

kA

25

31.5

25

31.5

Rated peak withstand current

kA

63

80

63

80

Gas insulating system

 

Insulating gas

SF₆

Rated service pressure(at 20℃,gauge)

MPa

0.04

Least service pressure(at 20℃, gauge)

MPa

0.02

Protection degree provided by enclosure

 

Sealing compartments

IP65

Control compartment

IP4X

Outline dimension

Width

Height

Depth

mm

#460
2100
1500

600
2100
1500

700/800
*2300
2100

800
2650
2100

Note:

#If equipped with PT,the width is 600.

*For upper PT scheme,the height of cubicle is 2750.

Main parameters of matched VS1X0 and VS1X2 VCB

Rated insulation level

Power frequency withstand voltage(1min)

kV

42148

95/118

Lightning impulse withstand voltage(peak)

kV

75/85

185/215

Rated frequency

 

Hz

50

Rated current

 

A

630

1250

1250

2500

Rated short time withstand current

 

25

31.5

25

31.5

Rated peak withstand current

 

63

80

63

80

Rated short circuit duration

s

4

Rated breaking current

kA

25

31.5

25

31.5

Rated breaking current for single back to back capacitor bank

A

630/400

Mechanical life

Circuit breaker

times

20000

Three-position switch

 

2000

Related Products
Welcome to tell us your needs
Submit
Send Inquiry
Submit

We provide bespoke industry solutions for diverse sectors.

Contact Us

Wechat/WhatsApp:

+86-137 5141 1282(Ata Rahimi)

Email:

rahimi@paires-tech.com

Address:

Room 430, Building 1, No. 6, Headquarters 1st Road, Songshan Lake Park, Dongguan City, Guangdong Province.

Copyright © Dongguan Paires Equipment Co., Ltd., Technical Support: Shangxian Sitexml