If you have any questions, please contact us.

Get in touch
Home Products Power Distribution System Series KYN96-40.5(Z) Withdrawable Metalclad AC Switchgear

Series KYN96-40.5(Z) Withdrawable Metalclad AC Switchgear

Series KYN96-40.5(Z) Withdrawable Metalclad AC Switchgear
Product Overview

KYN96-40.5 series withdrawable metalclad AC switchgears are mainly used for the power transmission of power plant and medium or small-scale power generators, and for the power distribution of industrial and mining enterprises, for the power transmission of secondary substation of electrical system etc., to fulfill the control,protection and monitor. The KYN96 complies with the requirement of standards such as IEC 62271-200 and GB 3906 and DL/T 404,etc. its rated current ranges from 630A to 2500A, The main VCB inside can be of that came from JV company or from domestic company.

·Compact in structure, strong in mechanical strength, safe and reliable in service. Its width is 1200mm only.

·Equipped with mid-set vacuum circuit breaker with solid-insulated embedded-poles

·Equipped with a special rotating and folding movable metal shutter

·The cubicle can meet all requirement of service with its reliable insulation by electricfield uniform and electric screen design

Main paramenters

Main paramenters of the switchgear

Item

Unit

Parameters

Rated voltage

kV

40.5

Rated insulation level

1min
Power frequency withstand voltage (1 min.)

P to P, P to E, across opened contact of CB

kV

95

Isolating breaker

118

Lightning withstand voltage

P to P, P to E, across opened contact of CB

185

Isolating breaker

215

1min Power frequency withstand voltage on auxiliary circuit (1 min.)

2

Rated frequency

Hz

50

Rated current of VCB

A

630 1250 1600 2000 2500

Rated current of switchgear

A

630 1250 1600 2000 2500

Rated current of main busbar

A

2500

Rated peak withstand current

kA

63 80

Rated short time withstand current

kA

25 31.5

Rated short circuit duration

s

4

Rated short circuit breaking current

kA

25 31.5

Rated short circuit making current

kA

63 80

Service Continuity Losing grade

LSC2B

IP code

Enclosure

IP4X

CB compartment with opened door

IP2X

Isolating sheet

PM

Protection requirement of entering each compartment

Enter into busbar compartment

Special tools must be used.

Enter into cable compartment

Accord with interlock specification and use special tools

Enter into other high-voltage compartment

Accord with interlock specification and use special tools

Dimension

Width

mm

1200

Depth

mm

2500 / 2800

Height

mm

2400

 

Main paramenters of Embedded Pole VCB

Item

Unit

Parameters

Rated voltage

kV

40.5

Rated insulation level

1min Power frequency withstand voltage (1 min.)

kV

95

Lightning withstand voltage

185

Rated frequency

Hz

50

Rated current

A

630 1250 1600 2000 2500

Rated symmetrical short circuit breaking current

kA

25 31.5

Rated short time withstand current (4 seconds, RMS)

kA

25 31.5

Rated peak withstand current

kA

63 80

Rated short circuit making current(peak)

kA

63 80

Classification on capacitive switching currents

Class

C2

Classification on a function of electrical endurance

E2

Classification on mechanical endurance

M2

Rated operation sequence

 

O-0.3s-CO-180s-CO

Rated operation voltage

Close coil

V

DC 220、110 / AC 220、110

Open coil

DC 220、110 / AC 220、110

Motor charging power

W

90

Motor charging rated voltage

V

DC 220、110 / AC 220、110

Charging time

s

≤15

Related Products
Welcome to tell us your needs
Submit
Send Inquiry
Submit

We provide bespoke industry solutions for diverse sectors.

Contact Us

Wechat/WhatsApp:

+86-137 5141 1282(Ata Rahimi)

Email:

rahimi@paires-tech.com

Address:

Room 430, Building 1, No. 6, Headquarters 1st Road, Songshan Lake Park, Dongguan City, Guangdong Province.

Copyright © Dongguan Paires Equipment Co., Ltd., Technical Support: Shangxian Sitexml